STREAMER Lightning Strike Counter (LSC) is meant to count the number of lightning strikes based on the current flowing in a conductor . The 250A high sensitivity Surge Counter can be installed easily on the ground leads even on existing installations thanks to its split core transformer.
The counter display can be mounted top, bottom, back, or strapped up to 20 m from the measurement point. The device complies to the IEC 62561. Thanks to its IP67, housing, rugged materials and self power, the LSC is suitable for outdoor and hazardous atmospheres.
Key features
- High measurement performance: from 250A minimum to 100kA detection
- Outdoor device : IP67
- No maintenance : self powered device, no battery
- Easy cable installation : split core current transformer, 5 to 25mm cable diameter
- Easy counter installation : bottom, top, back or strap mounting. Up to 20m cable length.
- Durable device : glass window, stainless steel & HDPE plastic
Air gap, mm | 0 | 2 | 4 | 6 | 10 | 15 | 20 |
Diameter of rod/conductor, mm | <16 | 16.1 | 16.5 | 17.1 | 18.8 | 21.9 | 25.6 |
Minimum discharge current, 8/20us, A
Conductor length | 3 m | 250 | 350 | 450 | 500 | 600 | 650 | 700 |
10 m | 250 | 370 | 500 | 600 | 700 | 800 | 900 | |
20 m | 350 | 400 | 600 | 700 | 900 | 1000 | 1000 |
Scope of Application
Installation
Technical characteristics
REFERENCE | VALUE |
CONDUCTOR DIAMETER RANGE, mm | 5 to 16 | 35 to 150mm2 |
MAXIMUM DISTANCE BETWEEN DISPLAY AND SENSOR | 3m |
INSTALLATION ON THE CONDUCTOR | in parallel – clamped |
MINIMUM DISCHARGE PEAK CURRENT DETECTED – 8/20us waveform – IEC 62561-6 | 250A |
MAXIMUM DISCHARGE PEAK CURRENT DETECTED – 10/350us waveform – IEC 62561-6 | 100 kA |
MINIMUM NUMBER STROKE REGISTRATION RATE | ≥ 2 counts/sec. |
MINIMUM TIME BETWEEN 2 STROKE FOR REGISTRATION, RESPONSE TIME | 20ms |
VOLTAGE DROP ON TERMINALS | < 1 V |
LONG DURATION CURRENT WITHSTAND CAPABILITY | 2500A for 4ms |
HIGH CURRENT WITHSTAND CAPABILITY | 100 kA |
FREQUENCY, Hz | 47 to 63 |
NUMBER OF DIGITS ON DISPLAY | 6 |
TYPE OF DISPLAY | MECHANICAL |
BATTERY POWER SUPPLY | NO |
SELF POWERED | YES |
RESET COUNTER METHOD | NO |
MEMORY ROM – Storage of last counter value | NO |
WEIGHT, kg | 1Kg |
ENVIRONMENTAL CONSTRAINTS
TEMPERATURE – °C | Class C2: -40 to +70 |
PROTECTION CLASS | IP67, NEMA 4X |
TEMPERATURE CHANGE RATE – °C/min | Class C2: 1,0 |
RELATIVE HUMIDITY – % | Class C2: 10 to 100 |
MAX ABSOLUTE HUMIDITY – g/m3 | Class C2: 35 |
MAX ALTITUDE – m | 2000 |
ATMOSPHERIC PRESSURE – kPa | 70 to 106 |
STANDARDS/TEST | IEC 62561-6:2018 |
LABEL INCLUDES | Harware version number, serial number, manufacturing batch |
UV STABILIZED HOUSING | YES |
STAINLESS METAL | YES |
TYPE OF SURGE COUNTER as per IEC 62561-6:2018 | Type 1 and Type 2; outdoor |